Home    15KV URD Cable
15KVURDCable

15KV URD Cable

15KV URD Cable


1/0 Stranded Aluminum/ Copper Conductor 15KV URD, 133%, Full Neutral

Applications:
1) 15KV URD cable is primary used for underground distribution, in direct burial or installed in conduit.

2) 15KV URD cable is suitable for use in wet or dry locations.

3)URD cable is to be used at 15,000 volts or less and not to exceed 90°C temperature in normal use.


CONSTRUCTION
Conductor: stranded Aluminum / Copper wire Rated voltage: 15kV
Strand shield: extruded semi-conducting strand shield Operating temperature: 90℃
Insulation: cross-linked polyethylene short-circuit operating temperature: 250℃
Insulation shield: extruded semi-conducting insulation shield
Neutral wires: 33% copper concentric neutral wires Maximum short circuit time: 5 seconds
Jacket: Non-conducting low density PE encapsulating jacket

Technical Data

Weight 1000 feet (lbs.)

Allowable Ampacities+

Phase Conductor

Neutral

Thickness Per Cond. (mils)

Nominal Diameter (mils)

Size (AWG or kcmil)

Insul. Shield min. Point

Bare Phase Cond.

Over Insul. Shield

Strand- ing

No. of Wires

Size (AWG)

Nominal Insul.

Approx. Jkt.

Over Insul.

Comp. Cable

Comp. Cable

Direct Burial

In Ducts

ALUMINUM CONDUCTOR - 100% INSULATION LEVEL

2

Solid

10

14

175

30

50

258

653

733

961

485

168 *

119 *

2

7

10

14

175

30

50

283

678

758

986

504

168 *

119 *

1

Solid

13

14

175

30

50

289

685

765

993

555

193 *

137 *

1

19

13

14

175

30

50

322

718

798

1026

577

193 *

137 *

1/0

Solid

16

14

175

30

50

325

720

800

1028

629

218 *

155 *

1/0

19

16

14

175

30

50

352

748

828

1056

648

218 *

155 *

2/0

19

20

14

175

30

50

395

790

870

1098

745

248 *

177 *

3/0

19

25

14

175

30

50

443

838

918

1146

862

284 *

201 *

4/0

19

20

12

175

30

50

498

893

973

1234

1042

324 *

230 *

250

37

16

10

175

30

50

558

963

1043

1346

1268

360 *

257 *

350

37

18

14

175

40

50

661

1068

1168

1396

1118

389 * *

319 * *

500

37

25

14

175

40

50

789

1193

1293

1521

1419

468 * *

384 * *

750

61

24

12

175

40

80

968

1383

1483

1798

2030

569 * *

468 * *

1000

61

20

10

175

40

80

1117

1530

1630

1988

2567

642 * *

542 * *

1250

91

25

10

220

55

80

1250

1765

1895

2253

3278

688 * *

604 * *

1500

91

30

10

220

55

80

1370

1885

2015

2373

3762

726 * *

637 * *

COPPER CONDUCTOR - 100% INSULATION LEVEL

2

Solid

16

14

175

30

50

258

653

733

961

697

210 *

150 *

2

7

16

14

175

30

50

283

678

758

986

719

210 *

150 *

1

Solid

20

14

175

30

50

289

685

765

993

815

240 *

171 *

1

19

20

14

175

30

50

322

718

798

1026

841

240 *

171 *

1/0

Solid

25

14

175

30

50

325

720

800

1028

959

273 *

194 *

1/0

19

25

14

175

30

50

362

758

838

1066

991

273 *

194 *

2/0

19

20

12

175

30

50

405

800

880

1142

1204

313 *

224 *

3/0

19

25

12

175

30

50

456

853

933

1194

1437

358 *

255 *

4/0

19

20

10

175

30

50

512

908

988

1291

1768

410 *

293 *

250

37

24

10

175

30

50

558

963

1043

1346

2047

446 *

322 *

350

37

18

12

175

40

50

661

1068

1168

1429

2027

489 * *

400 * *

500

37

26

12

175

40

50

789

1193

1293

1554

2722

577 * *

472 * *

750

61

25

10

175

40

80

968

1383

1483

1840

3990

649 * *

532 * *

1000

61

26

9

175

40

80

1117

1530

1630

2013

5136

720 * *

630 * *

1250

91

26

8

220

55

80

1250

1765

1895

2306

6535

760 * *

667 * *

+ Ampacities shown assume use of 100% load factor, 60Hz current, 36″ burial depth, 20°C ambient temperature, 90°C

conductor temperature, earth RHO 90, insulation and shield RHO 400

* Full neutral construction (Ampacities assume - single phase circuit, one cable)

**1/3 neutral cable (Ampacities assume - three phase circuit, 3 cables triplexed, multi-point grounding per ICEA methods)